Compliance report EN 50160 Power quality monitoring IEC 62586 Power quality measurement IEC 61000-4-30 : class S
|
|
device application |
Power monitoring WAGES metering
|
|
type of measurement |
Power factor (total) Apparent power (total) Active and reactive power (total) Active and reactive power (per phase, rms) Apparent power (per phase, rms) Power factor (per phase, rms) Voltage Current Frequency
|
|
[Us] rated supply voltage |
90...415 V AC +/- 10 % (45...65 Hz) 120...300 V DC +/- 10 %
|
|
network frequency |
60 Hz 50 Hz
|
|
[In] rated current |
10 A 5 A 1 A
|
|
poles description |
1P + N 3P 3P + N
|
|
power consumption in VA |
18...36 VA at 415 V AC
|
|
display type |
Colour TFT LCD
|
|
display resolution |
320 x 240 pixels QVGA
|
|
sampling rate |
256 samples/cycle
|
|
measurement current |
50 mA...10 A
|
|
analogue input type |
Current (impedance 0.3 mOhm) Voltage (impedance 5 MOhm)
|
|
measurement voltage |
57...400 V AC 42...69 Hz between phase and neutral 100...690 V AC 42...69 Hz between phases
|
|
frequency measurement range |
42...69 Hz
|
|
number of inputs |
3 digital 30 V AC 3 digital 60 V DC
|
|
measurement accuracy |
+/- 0.2 % active energy +/- 0.1 % voltage +/- 0.1 % current
|
|
accuracy class |
Class 0.2 (active energy according to ANSI C12.20) Class 0.2S (active energy according to IEC 62053-22) Class 0.2 (active power according to IEC 61557-12) Class 0.5S (reactive energy according to IEC 62053-24) Class 0.5 (power factor according to IEC 61557-12) Class 0.2 (voltage according to IEC 61557-12) Class 0.2 (current according to IEC 61557-12)
|
|
number of outputs |
1 pulse
|
|
information displayed |
Voltage Current Frequency Power Energy consumption Harmonic distortion
|
|
communication port protocol |
DNP3 IEC 61850 Modbus RTU 2-wire, : 115 kbauds, ION 2-wire, : 115 kbauds, Modbus TCP/IP Ethernet Modbus TCP/IP daisy chain : 10/100 Mbit/s, RSTP 801.1d 2004
|
|
communication port support |
Ethernet RS485 (screw terminal block)
|
|
data recording |
Waveform logs Alarm logs Harmonics logs Time stamping Sag and swell logs Data logs Trending/forecasting Event logs GPS synchronisation Sequence of event recording Min/max of instantaneous values
|
|
memory capacity |
512 MB
|
|
web services |
HTTP server Alarm notification by e-mail Customizable home page File upload/download via FTP
|
|
communication service |
SNMP NTP time synchronization SMTP e-mail notification RSTP support
|
|
mounting mode |
Flush-mounted
|
|
mounting support |
Framework
|
|
installation category |
III
|
|
isolation voltage |
IEC 61010-1 : CAT III, 400...690 V ed. 3 EN 61010-1 : CAT III, 400...690 V ed. 3 UL 61010-1 : CAT III, 347...600 V ed. 3 CSA C22.2 No 61010-1 : CAT III, 347...600 V ed. 3
|
|
standards |
IEC 62053-22 IEC 62052-11 IEC 62053-24 IEC 61557-12
|