Previous image Next image
Zoom image

PM82401 Multifunction with waveform capture

PowerLogic PM82401 96x96 panel mount meter.

MID-approved, Class 0.2S, secondary CT rating 1/5/10A, 690V, harmonic analysis up to 63rd harmonic waveform capture, logging, multiple i/o including Ethernet and Modbus.

In stock (10 items available)
  • £1584.92
  • Would you like to have your panel meter mounted on the door of a pre-wired enclosure (PXMP1/XMP1), including 3 fuse holders, fuses, neutral and CT disconnects?
  • Weight
    0.6 kg
  • SKU

Schneider PowerLogic 82401 Class 0.2 Ethernet enabled multifunction 3ph 96x96mm Panel Meter. An exceptionally featured quality and value Ethernet connected billing meter. Compact MID-approved meter for monitoring or billing import and export energy, power management, harmonic analysis . Modbus TCP comms. Pulse and selectable 35-parameter multi-condition alarm outputs. One digital output. Up to 63rd harmonic THD and individual current and voltage harmonics. 512MB memory. 690V inter-phase metering voltage, 400V phase-neutral. 1, 5 or 10 Amp CT. Calculated neutral current. Voltage sag and swell detection.


Compliance report EN 50160
Power quality monitoring IEC 62586
Power quality measurement IEC 61000-4-30 : class S
device application
Power monitoring
WAGES metering
type of measurement
Power factor (total)
Apparent power (total)
Active and reactive power (total)
Active and reactive power (per phase, rms)
Apparent power (per phase, rms)
Power factor (per phase, rms)
[Us] rated supply voltage
90...415 V AC +/- 10 % (45...65 Hz)
120...300 V DC +/- 10 %
network frequency
60 Hz
50 Hz
[In] rated current
10 A
5 A
1 A
poles description
1P + N
3P + N
power consumption in VA
18...36 VA at 415 V AC
display type
Colour TFT LCD
display resolution
320 x 240 pixels QVGA
sampling rate
256 samples/cycle
measurement current
50 mA...10 A
analogue input type
Current (impedance 0.3 mOhm)
Voltage (impedance 5 MOhm)
measurement voltage
57...400 V AC 42...69 Hz between phase and neutral
100...690 V AC 42...69 Hz between phases
frequency measurement range
42...69 Hz
number of inputs
3 digital 30 V AC
3 digital 60 V DC
measurement accuracy
+/- 0.2 % active energy
+/- 0.1 % voltage
+/- 0.1 % current
accuracy class
Class 0.2 (active energy according to ANSI C12.20)
Class 0.2S (active energy according to IEC 62053-22)
Class 0.2 (active power according to IEC 61557-12)
Class 0.5S (reactive energy according to IEC 62053-24)
Class 0.5 (power factor according to IEC 61557-12)
Class 0.2 (voltage according to IEC 61557-12)
Class 0.2 (current according to IEC 61557-12)
number of outputs
1 pulse
information displayed
Energy consumption
Harmonic distortion
communication port protocol
IEC 61850
Modbus RTU 2-wire, : 115 kbauds,
ION 2-wire, : 115 kbauds,
Modbus TCP/IP
Ethernet Modbus TCP/IP daisy chain : 10/100 Mbit/s,
RSTP 801.1d 2004
communication port support
RS485 (screw terminal block)
data recording
Waveform logs
Alarm logs
Harmonics logs
Time stamping
Sag and swell logs
Data logs
Event logs
GPS synchronisation
Sequence of event recording
Min/max of instantaneous values
memory capacity
512 MB
web services
HTTP server
Alarm notification by e-mail
Customizable home page
File upload/download via FTP
communication service
NTP time synchronization
SMTP e-mail notification
RSTP support
mounting mode
mounting support
installation category
isolation voltage
IEC 61010-1 : CAT III, 400...690 V ed. 3
EN 61010-1 : CAT III, 400...690 V ed. 3
UL 61010-1 : CAT III, 347...600 V ed. 3
CSA C22.2 No 61010-1 : CAT III, 347...600 V ed. 3
IEC 62053-22
IEC 62052-11
IEC 62053-24
IEC 61557-12
Related products
Drop items here to shop
Product has been added to your cart
Schneider ElectricTyco ElectronicsABBKamstrupCarlo GavazziElsterCircutorDMMeteringEDMIIMEIskraemecoSmart ProcessSHM MeteringLovatoNorthern DesignLandis GyrSocomecHobut

NEW on the SHM shop – 96x96 or 72x72 meters can be bought with Plastic or Steel enclosures. Contact SHM if you need more than 1 meter in the panel.
All meters used for billing in the EU must be MID Approved. Find out what the Measuring Instruments Directive means to you.
SHM frequently find that CT are miswired when troubleshooting installations. This document might help you to install CT correctly.